fireman fire

Similar Posts

Leave a Reply

Your email address will not be published. Required fields are marked *

266 Comments

  1. What is the width of a final fire escape door? I heard that it has been increased to 1500mm???
    What is the thickness of such a door? I heard it is 25mm???
    And would such a door with its width at 1500mm become a rebated double door???

  2. Rob Rademeyer says:

    Hi

    We are busy renovating the middle floor of a 3-floor building where we rent the middle & top floors for business pursuits i.e. we are only occupied from 08h00 to 18h00 Monday to Friday.

    The architect has told us that we require a fire door to be fitted to the [glass & aluminium] entrance way on the middle floor. The entrance way is in a stairwell that services all three floors.

    There is a fully functioning fire escape at the back of each floor i.e. escape doors, & stairs to evacuation area.

    There is NO fire door on the ground or top floors.

    Can you please advise whether or not the architect is correct, or where one can review the regulations on this issue [for Cape Town]. This must be something other than the SANS 10400 documention which only deals with the TYPE of fire door to be fitted, but not WHEN such a fire door should be fitted.

    Thanks in advance
    Rob

  3. Hi, hope the forum can assist. I am trying to find legislation where it specifically says that companies need to do fire training/Evac training. This does not exist in the Ohs act and was directed to the sans act. Any assistance would be greatly appreciated.

  4. Johan Germishuizen says:

    What should the distance be between tempory housing erected by local municipalities and under wich section of sans will i find it.

  5. When it comes to fire regulations the local municipality building inspectors must inspect the site and make their recommendations because each and every site is unique and there cannot be one rule for all.

  6. This is specific to each installation. The SANS10400 Part-W says: “so many isolating valves shall be provided to control the flow of water to the installation, and to such points within the installation, as the local authority may require” So it is up to each site to be inspected by the local authority and make their reccomendations. There are specialist fire installation companies that can advise you about your specific site.

  7. This is a tricky one! 😀 I would suggest contacting one of the major laminate glass manufacturers as they will have their Agrement certificates to hand and will be able to tell you right away. Here are two: Glass South Africa and PFG

  8. Hi All. I have a client that wants to build a new garage attached to his house that is going to house an Astin Martin. He wants to have glazing between the house and the garage so that it is visible from the inside – are there applicable Fire Regulations here? I know that a half hour rating is needed on the door but have no experience with glazing between. Is this even allowed? Thanks.

  9. Thanks for the extra advice Marius, much appreciated.

  10. The same on this Antonie, all contributions are welcome. Ntobe Fire Control contact: 013 754 6674

  11. Thanks for giving advice on this Antonie, as it is out of our field all contributions are welcome. Ntobe Fire Control contact: 013 754 6674

  12. Thanks for the heads-up on this Antonie. I see you are with Ntobe Fire Control and customers can contact you on 013 754 6674

  13. Antoine Jaume says:

    Sprinkler Pumps need to be tested on a weekly basis.
    Pumps must be serviced every year
    Sprinkler control valves must be serviced minimum every three years

  14. Antoine Jaume says:

    Fire Sprinkler Control Valve must be serviced by an ASIB approved person every three years,
    The Fire Sprinkler Pump needs to be serviced every year.

    SANS 10287

  15. Antoine Jaume says:

    The cheapest would be a normal DCP powder Extinguisher. You can use them for Class A – (Ash), Class B – (Liquid Fires) and Class C – Electrical fires.

    The problem is the white powder – the clean-up afterwards could be tedious.

    A CO2 extinguisher can also be used – but with caution.

    Best Regards

  16. The SANS 10400 deals with the construction, quantities and placement of fire equipment and not with the class of extinguisher. You will need to see SANS 1910. As far as I am aware the two types that are used for electrical fires are CO2 (carbon dioxide) and Dry Chemical Powder portable extinguishers. Contact one of the experts: advancedfst.co.za/Contact

  17. Ray Martin says:

    What extinguishers are required in the case of an electric fire? Urgent response please.

  18. The SANS 10400-Part T only deals with the building, escape routes, number of extinguishers per sq m etc etc. The maintenance of sprinklers is part of a different SANS that we do not deal with on this site but it could be SANS 10287 that covers maintenance by a competent person.

  19. paul morris says:

    Can you please confirm what section in the NBR Fire Protection Systems – service date for sprinkler systems?

    Need urgent reply.

    Thank You.

  20. The fire regulations are very strict and if that is what the fire marshall says must happen then yes the sprinkler needs to work. You can read more here: fire-protection BTW if the sprinkler is not working then you will not be covered by your insurance if you do have a fire.

  21. Hi
    I would like to find out something. WE have moved to a new business premises abut 7 years ago. We use the warehouse for the storage of diapers and pads. WE have an existing sprinkler system bt it is not operational. According to the fire Marshall that gave us an inspection report he says that we need to have the sprinklers in working order. The building is more than 200m square
    Is it correct as per the fire marshall and could you give me some reference points please

  22. Hi,

    Could you please tell me what the requirements for fire suppression and protection is for commercial kitchens.

  23. chris evert says:

    Can any of you tell me at a pyrotechnical plant (factory) what the requirement is in distance between fire hydrants.